This paper describes how direct evaporative coolers can be used to improve the energy efficiency of air-cooled chillers in various operating conditions and with different strategies for staging condenser fans. These coolers are installed in front of air-cooled condensers to precool outdoor air before entering the condensers. A simulation analysis on an air-cooled chiller equipped with a direct evaporative cooler showed that when head pressure control is used, the cooler enables the condensing temperature to drop by 2.1–6.2°C, resulting in a 1.4-14.4% decrease in chiller power and a 1.3–4.6% increase in the refrigeration effect. When the chiller with the cooler operates under condensing temperature control, where condenser effectiveness is enhanced by staging all condenser fans, there is a savings in chiller power of 1.3-4.3% in some operating conditions in which the drop in compressor power exceeds the additional condenser fan power due to the pressure drop across the cooler.
Skip Nav Destination
e-mail: befwyu@polyu.edu.hk
Article navigation
August 2005
Technical Briefs
Application of Direct Evaporative Coolers for Improving the Energy Efficiency of Air-Cooled Chillers
F. W. Yu,
e-mail: befwyu@polyu.edu.hk
F. W. Yu
Department of Building Services Engineering, The Hong Kong Polytechnic University, Hung Hom, Hong Kong, China
Search for other works by this author on:
K. T. Chan
K. T. Chan
Department of Building Services Engineering, The Hong Kong Polytechnic University, Hung Hom, Hong Kong, China
Search for other works by this author on:
F. W. Yu
Department of Building Services Engineering, The Hong Kong Polytechnic University, Hung Hom, Hong Kong, China
e-mail: befwyu@polyu.edu.hk
K. T. Chan
Department of Building Services Engineering, The Hong Kong Polytechnic University, Hung Hom, Hong Kong, China
Contributed by the Solar Energy Division of THE AMERICAN SOCIETY OF MECHANICAL ENGINEERS. Manuscript received by the ASME Solar Energy Division March 24, 2004; final revision July 14, 2004. Associate Editor: V. C. Mei.
J. Sol. Energy Eng. Aug 2005, 127(3): 430-433 (4 pages)
Published Online: July 20, 2005
Article history
Received:
March 24, 2004
Revised:
July 14, 2004
Online:
July 20, 2005
Citation
Yu , F. W., and Chan , K. T. (July 20, 2005). "Application of Direct Evaporative Coolers for Improving the Energy Efficiency of Air-Cooled Chillers ." ASME. J. Sol. Energy Eng. August 2005; 127(3): 430–433. https://doi.org/10.1115/1.1866144
Download citation file:
Get Email Alerts
A Nonintrusive Optical Approach to Characterize Heliostats in Utility-Scale Power Tower Plants: Camera Position Sensitivity Analysis
J. Sol. Energy Eng (December 2024)
A Solar Air Receiver With Porous Ceramic Structures for Process Heat at Above 1000 °C—Heat Transfer Analysis
J. Sol. Energy Eng (April 2025)
View Factors Approach for Bifacial Photovoltaic Array Modeling: Bifacial Gain Sensitivity Analysis
J. Sol. Energy Eng (April 2025)
Resources, Training, and Education Under the Heliostat Consortium: Industry Gap Analysis and Building a Resource Database
J. Sol. Energy Eng (December 2024)
Related Articles
Capacity Control for Refrigeration and Air-Conditioning Systems: A Comparative Study
J. Energy Resour. Technol (March,2001)
Implementation of Microchannel Evaporator for High-Heat-Flux Refrigeration Cooling Applications
J. Electron. Packag (March,2006)
Controls and Diagnostics for Air Distribution Systems
J. Sol. Energy Eng (August,2003)
Related Proceedings Papers
Related Chapters
Thermodynamic Performance
Closed-Cycle Gas Turbines: Operating Experience and Future Potential
Interlude
Turbo/Supercharger Compressors and Turbines for Aircraft Propulsion in WWII: Theory, History and Practice—Guidance from the Past for Modern Engineers and Students
Threshold Functions
Closed-Cycle Gas Turbines: Operating Experience and Future Potential